Electronic pressure measurement

Pressure transmitter for general industrial applications Model A-10
WIKA data sheet PE 81.60

Applications
■ Machine building ■ Machine tools ■ Measurement and control technology ■ Hydraulics and pneumatics ■ Pumps and compressors

Special features
■ Measuring ranges from 0 … 1 to 0 … 600 bar ■ Non-linearity 0.25 % or 0.5 % ■ Output 4 ... 20 mA, DC 0 ...10 V, DC 0 ... 5 V and others ■ Electrical connection: Angular connector form A and C,

■ Process connection G ¼ A DIN 3852-E, ¼ NPT and others

circular connector M12 x 1, cable outlet 2 m

Pressure transmitter model A-10

Description
The model A-10 pressure transmitter for general industrial applications is not only notable for its compact design, but it also offers excellent quality atan extremely competitive price. The user can choose between a non-linearity of 0.25 % and 0.5 %. A free test certificate provides information on the measuring points recorded during manufacture. The model A-10 is set up for worldwide use through the international cULus and GOST certification. The various pressure units and process connections required for particular operating conditions areavailable at short notice.

WIKA data sheet PE 81.60 ∙ 02/2012
Data sheets showing similar products: Pressure transmitter for general applications; model S-10; see data sheet PE 81.01

Page 1 of 8

Measuring ranges
Relative pressure
bar Measuring range Overpressure limit Measuring range 0 ... 1 2 0 ... 40 0 ... 1.6 3.2 0 ... 60 0 ... 2.5 5 0 ... 100 0 ... 4 8 0 ... 160 0 ... 6 12 0 ... 250 0... 10 1) 20 0 ... 400 32 0 ... 16 1) 0 ... 25 1) 50

Overpressure limit psi

80

120 60

200 60

320

500

Measuring range Overpressure limit Measuring range

0 ... 15 30 0 ... 500

0 ... 25 0 ... 1,000

0 ... 30 0 ... 1,500

0 ... 50 100 0 ... 2,000

0 ... 100 200 0 ... 3,000

0 ... 160 1) 290 0 ... 5,000

800

1,200 400

0 ... 600 0 ... 200 1) 0 ... 300 1)

600Overpressure limit

1,000

1,740

2,900

4,000

6,000

10,000

17,400

0 ... 10,000

Absolute pressure
bar psi Overpressure limit Overpressure limit Measuring range 2 0 ... 1 3.2 60 0 ... 1.6 5 0 ... 2.5 8 0 ... 4 12 0 ... 6 20 0 ... 10 32 0 ... 16 50 0 ... 25

Measuring range

30

0 ... 15

0 ... 25

60

0 ... 30

100

0 ... 50

200

0 ... 100

2900 ... 150

400

0 ... 200

600

0 ... 300

Vacuum and +/- measuring range
bar Measuring range Overpressure limit Measuring range Overpressure limit psi Measuring range Overpressure limit Measuring range -1 ... 0 2 -1 ... +9 20 -30 inHG ... 0 -30 inHG ... +160 30 -1 ... +0.6 3.2 32 -1 ... +15 -30 inHG ... +15 -30 inHG ... +200 450 60 -1 ... +1.5 5 -1 ... +24 50 -30 inHG ... +30 -30 inHG... +300 600 60 -30 inHG ... +60 150 -30 inHG ... +100 250 -1 ... +3 8 -1 ... +5 12

Overpressure limit

350

1 ) If the medium water is measured, a higher overpressure limit is recommended.

The given measuring ranges are also available in kg/cm2, MPa and kPa. Other measuring ranges available on request Vacuum resistance Yes

Output signal
Signal type
Current (2-wire) Voltage (3-wire)Signal
4 ... 20 mA DC 0 ... 10 V DC 0 ... 5 V DC 1 ... 5 V DC 0.5 ... 4.5 V DC 0.5 ... 4.5 V

Ratiometric (3-wire)

Other output signals available on request Depending on the signal type the following loads apply: Signal type
Current (2-wire) Voltage (3-wire) Ratiometric (3-wire)

Load in Ω
≤ (power supply - 8 V) / 0.02 A > maximum output signal / 1 mA > 4.5k

Page 2 of 8

WIKAdata sheet PE 81.60 ∙ 02/2012

Voltage supply
Power supply Output signal
4 ... 20 mA DC 0 ... 10 V DC 0 ... 5 V DC 1 ... 5 V DC 0.5 ... 4.5 V DC 0.5 ... 4.5 V ratiometric
1) Not possible with non-linearity 0.25 % BFSL

Power supply
Standard DC 8 ... 30 V DC 14 ... 30 V DC 8 ... 30 V DC 8 ... 30 V DC 8 ... 30 V DC 5 V ± 10 %

Option DC 8 ... 35 V 1) DC 14 ... 35 V DC 8 ... 35 V DC 8 ......